BENEFITS FROM THE USE OF WIRE-COIL INSERTS IN WATER TRANSITIONAL AND LOW TURBULENT FLOW The Influence of the Wire-Coil Pitch

creativework.keywordsbenefits, heat transfer enhancement, pitch of wire-coil insert, transitional and low turbulent flow
creativework.publisherSerbian Society of Heat Transfer Engineersen
dc.contributor.authorZimparov V.
dc.contributor.authorBonev P.
dc.contributor.authorAngelov M.
dc.contributor.authorHristov J.
dc.date.accessioned2024-07-10T14:27:05Z
dc.date.accessioned2024-07-10T14:50:11Z
dc.date.available2024-07-10T14:27:05Z
dc.date.available2024-07-10T14:50:11Z
dc.date.issued2022-01-01
dc.description.abstractFive wire-coil inserts with fixed wire diameter and different pitches, fitted inside a round tube have been experimentally studied in a transitional and low turbulent flow. Water was used as a working fluid at a wide range of flow conditions: 103 < Re < 104 and 3.9 < Pr < 10.0. The geometrical parameters of the inserts are: e/Di = 0.070, and p/e = 6.7, 9.0, 10.0, 12.5, and 15.0. The variation of the friction factor and heat transfer coefficients have been obtained and compared with those of the smooth pipe. Performance evaluation criteria for the cases FG-1a, FG-2a, and VG-2a have been used to evaluate the maximum and real benefit that can be obtained. The greatest benefit can be achieved with the pitch of the wire-coil insert p/e = 10.0.
dc.identifier.doi10.2298/TSCI211206060Z
dc.identifier.issn0354-9836
dc.identifier.scopusSCOPUS_ID:85135534789en
dc.identifier.urihttps://rlib.uctm.edu/handle/123456789/734
dc.language.isoen
dc.source.urihttps://www.scopus.com/inward/record.uri?partnerID=HzOxMe3b&scp=85135534789&origin=inward
dc.titleBENEFITS FROM THE USE OF WIRE-COIL INSERTS IN WATER TRANSITIONAL AND LOW TURBULENT FLOW The Influence of the Wire-Coil Pitch
dc.typeArticle
oaire.citation.issue4
oaire.citation.volume26
Files
Collections